Air-Insulated Switchgear (AIS) NXAIR for rated voltages of 20/10(6) kV, up to 3150A

Air-Insulated Switchgear (AIS) NXAIR family for rated voltages of 20/10(6) kV, up to 3150A represents factory-assembled, metal-enclosed, type-tested circuit-breaker switchgear, used for indoor installation mainly at the primary distribution level, e.g.:
Public Power Supply
- Power supply companies
- Energy producers
- System Operators
Industry and Offshore
- Cement industry
- Steel industry
- Mining industry
- Petroleum industry and offshore installations
- Diesel power plants
- Emergency power supply installations
- Electrochemical plants and chemical industry
- Pipeline installations
Air-Insulated Medium-Voltage Switchgear NXAIR is factory-assembled, type-tested, metal-enclosed and metal-clad switchgear for indoor installation according to IEC 62261-200.
All switchgear types of the NXAIR family are approved with internal arc classification IAC A FLR, loss of service continuity category LSC 2B and partition class PM.
Switchgear with SION vacuum circuit-breakers has the benefits of safety, reliability, increased productivity and efficiency.
Air-Insulated Switchgear is time-tested by many years of practical experience in operation worldwide.
Customer benefit features
Smooth Operation
- As insulating medium, air is always available
- Factory-assembled, type-tested switchgear
- Use of maintenance-free vacuum circuit-breakers or contactors
- Type testing of the vacuum circuit-breaker and the make-proof earthing switch in the panel
- Pressure-resistant partitions (NXAIR technology)
- Flexibility regarding the low-voltage equipment (removable compartment, plug-in wires).
Optimal Personal Safety
- All operations with closed high-voltage door
- Logical mechanical interlocks prevent maloperation
- Switching, earthing and disconnecting devices as one functional unit
- Unambiguous position indicators and control elements on the high-voltage door
- Confinement of an internal arc to the respective compartment up to 50 kA, 1 s.
Increases Productivity
- Loss of service continuity category LSC 2B (separate partitions for busbar, connection and switching-device compartments)
- Positively driven shutters
- Use of standardized block-type current transformers
- Cable testing without isolating the busbar
- Functions such as establishment of the isolating distance, as well as feeder and busbar earthing, can be completely controlled from remote
- Confinement of an internal arc to the respective compartment
- Control cables in metallic wiring ducts.
Saves Money
- Use of maintenance-free vacuum circuit-breakers or contactors
- Maintenance-free switchgear within up to 10 years
- Interruption of operation reduced to a minimum by logical mechanical interlocking system
- Minimized space requirements (reduced building investments) due to compact design and flexible cable connection options and / or flexible pressure relief duct systems.